- Description
- Reviews (0)
Product description
Set of 12 MVSV gel cells, each of 2V and 1000Ah commercial capacity, supplied in 2 transport boxes. Allows battery banks of 12V or 24V to be configured by means of series and parallel connections, and is intended for stationary systems of high capacity that require reliable energy storage, continuous operation and flexibility to adapt the bank to the electrical characteristics of the installation.
Bank configurations
The standard configuration connects the 12 cells in series to obtain a bank of 24V and 998Ah nominal. They may also be arranged as two strings of 6 cells connected in parallel to configure a bank of 12V and 1996Ah nominal.
In a series connection the voltages are added and the capacity is maintained. In parallel the voltage is maintained and the capacities are added. To ensure balanced operation, all connected cells and strings must be of the same range, model, capacity and state of charge. New cells must not be combined with used units.
Technology and installation
Valve-regulated lead-acid technology keeps the electrolyte immobilised in gel and does not require water topping up. The cells may be installed in a vertical or horizontal position, always with the same orientation within the bank. In horizontal installations, each unit must be supported individually on a suitable rack along its entire surface. The recommended minimum spacing between cells is 10mm and the recommended maximum temperature difference between cells is 3°C.
Technical specifications
| Item | Value |
|---|---|
| Range | MVSV |
| Technology | Valve-regulated lead-acid with gel electrolyte |
| Number of cells | 12 |
| Nominal voltage per cell | 2V |
| Commercial capacity per cell | 1000Ah |
| Nominal technical capacity per cell | 998Ah in C10, up to 1.8V per cell at 20°C |
| Discharge current C10 per cell | 99.8A |
| Configuration of 24V | 998Ah nominal |
| Configuration of 12V | 1996Ah nominal |
| Number of terminal pairs per cell | 2 |
| Internal resistance per cell | 0.38m? |
| Short-circuit current per cell | 4850A |
| Float voltage | 2.30V per cell at 25°C |
| Float voltage for the configuration of 24V | 27.6V |
| Absorption voltage | 2.38V per cell at 25°C, for a maximum of 5 hours |
| Absorption voltage for the configuration of 24V | 28.5V |
| Charge compensation by temperature | ?5mV/°C per cell |
| Charge compensation for the configuration of 24V | ?60mV/°C |
| Guide charge current | Between 10A and 50A for each 100Ah of nominal capacity |
| Operating temperature | From ?20°C to 45°C |
| Nominal operating temperature | From 10°C to 30°C |
| Recommended operating temperature | 20°C |
| Absolute maximum temperature | 55°C |
| Storage temperature | From ?40°C to 55°C |
| Maximum dimensions per cell | 212 × 193 × 690mm |
| Casing height without terminals | 648mm |
| Installed length per cell | 221mm |
| Approximate weight per cell | 66kg |
| Approximate total weight of the 12 cells | 792kg |
| Terminals | F-M8 |
| Tightening torque of the M8 connections | 20 ± 1Nm |
| Casing material | Styrene-acrylonitrile copolymer |
| Casing flammability rating | UL 94 HB |
| Recommended minimum spacing between cells | 10mm |
| Recommended maximum temperature difference between cells | 3°C |
| Installation position | Vertical or horizontal |
| Approximate self-discharge | 2% monthly at 20°C |
Main features
- Set of 12 gel cells of the MVSV range.
- Configuration of 24V by connecting the 12 cells in series.
- Possibility of configuring a bank of 12V by means of two strings connected in parallel.
- Valve-regulated lead-acid technology.
- Electrolyte immobilised in gel.
- No need for water topping up.
- Designed for stationary systems of high capacity.
- Installation permitted in a vertical or horizontal position.
- Approximate self-discharge of 2% monthly at 20°C.
- Supplied in 2 transport boxes.