Set consisting of 48 MVSV gel cells of 2V and 580Ah, supplied in 4 transport boxes. Allows battery banks to be configured of 12V, 24V, 48V or 96V by means of series and parallel connections. It is intended for stationary systems of high capacity that require reliable energy storage, continuous operation and flexibility to adapt the battery bank to the electrical characteristics of the installation.
Each set of 12 cells of the MVSV range has a nominal voltage of 2V per cell and a commercial capacity of 580Ah. The standard configuration connects the 12 cells in series to obtain a bank of 24V and 582Ah nominal. They can also be arranged as two series of 6 cells connected in parallel to configure a bank of 12V and 1164Ah nominal.
Connection and balancing of the bank
In a series connection the voltages are added and the capacity is maintained. In parallel the voltage is maintained and the capacities are added. To ensure balanced operation, all cells and series connected must be of the same range, model, capacity and state of charge. New cells must not be combined with used units.
Technology and installation
Valve-regulated lead-acid technology keeps the electrolyte immobilised in gel and does not require water topping up. The cells can be installed in a vertical or horizontal position, always with the same orientation within the bank. In horizontal installations, each unit must be supported individually on a suitable rack along its entire surface.
Each transport box contains 1 set of 12 cells. The complete set of 48 cells is supplied in 4 transport boxes.
Main features
- Set of 12 gel cells of the MVSV range.
- 24V configuration by connecting the 12 cells in series.
- Possibility of configuring a bank of 12V by means of two series connected in parallel.
- Valve-regulated lead-acid technology.
- Electrolyte immobilised in gel.
- No need to top up with water.
- Designed for stationary systems of high capacity.
- Installation permitted in a vertical or horizontal position.
- Approximate self-discharge of 2% per month to 20°C.
- Supplied in 1 transport box.
Technical specifications
| Parameter | Value |
|---|---|
| Range | MVSV |
| Technology | Valve-regulated lead-acid with gel electrolyte |
| Number of cells | 12 |
| Nominal voltage per cell | 2V |
| Commercial capacity per cell | 580Ah |
| Technical nominal capacity per cell | 582Ah in C10, up to 1.8V per cell at 20°C |
| Discharge current C10 per cell | 58.2A |
| 24V configuration | 582Ah nominal |
| 12V configuration | 1164Ah nominal |
| Number of terminal pairs per cell | 1 |
| Internal resistance per cell | 0.47m? |
| Short-circuit current per cell | 4400A |
| Float voltage | 2.30V per cell at 25°C |
| Float voltage for the 24V configuration | 27.6V |
| Absorption voltage | 2.38V per cell at 25°C, for a maximum of 5 hours |
| Absorption voltage for the 24V configuration | 28.5V |
| Charge compensation by temperature | ?5mV/°C per cell |
| Charge compensation for the 24V configuration | ?60mV/°C |
| Guide charge current | Between 10A and 50A for each 100Ah of nominal capacity |
| Operating temperature | From ?20°C to 45°C |
| Nominal operating temperature | From 10°C to 30°C |
| Recommended operating temperature | 20°C |
| Absolute maximum temperature | 55°C |
| Storage temperature | From ?40°C to 55°C |
| Maximum dimensions per cell | 168 × 208 × 515mm |
| Case height without terminals | 473mm |
| Installed length per cell | 177mm |
| Approximate weight per cell | 39kg |
| Approximate total weight of the 12 cells | 468kg |
| Terminals | F-M8 |
| Tightening torque of the M8 connections | 20 ± 1Nm |
| Case material | Styrene-acrylonitrile copolymer |
| Case flammability rating | UL 94 HB |
| Recommended minimum spacing between cells | 10mm |
| Recommended maximum temperature difference between cells | 3°C |
| Installation position | Vertical or horizontal |
| Approximate self-discharge | 2% per month to 20°C |