- Description
- Reviews (0)
Product description
Set consisting of 6 MVSV gel cells of 2V and 750Ah, supplied in 1 transport box. Their series connection allows a 12V battery bank to be configured for high-capacity stationary systems. It is intended for stationary installations requiring a high storage capacity, continuous operation and a construction prepared for demanding applications.
Connection and configuration
Connecting the 6 cells in series allows a battery bank of 12V and 748Ah nominal to be configured: in a series connection the cell voltages are added and their capacity is maintained. To favour balanced operation, the connected units must be of the same range, model, capacity and state of charge. New cells must not be combined with used units.
Technology and installation
Valve-regulated lead-acid technology keeps the electrolyte immobilised in gel and does not require water topping up. The cells can be installed in a vertical or horizontal position, always with the same orientation within the bank. In horizontal installations, each unit must rest individually on a suitable frame along its entire surface.
Main features
- Set of 6 gel cells from the MVSV range.
- 12V configuration by connecting the 6 cells in series.
- Valve-regulated lead-acid technology.
- Electrolyte immobilised in gel.
- No need to top up with water.
- Designed for high-capacity stationary systems.
- Installation permitted in a vertical or horizontal position.
- Approximate self-discharge of 2% per month at 20°C.
- Supplied in 1 transport box.
Technical specifications
| Data | Value |
|---|---|
| Range | MVSV |
| Technology | Valve-regulated lead-acid with gel electrolyte |
| Number of cells | 6 |
| Nominal voltage per cell | 2V |
| Commercial capacity per cell | 750Ah |
| Technical nominal capacity per cell | 748Ah at C10, up to 1.8V per cell at 20°C |
| Discharge current C10 per cell | 74.8A |
| Series configuration of the 6 cells | 12V and 748Ah nominal |
| Number of terminal pairs per cell | 1 |
| Internal resistance per cell | 0.48m? |
| Short-circuit current per cell | 4300A |
| Float voltage | 2.30V per cell at 25°C |
| Float voltage for the 12V configuration | 13.8V |
| Absorption voltage | 2.38V per cell at 25°C, for a maximum of 5 hours |
| Absorption voltage for the 12V configuration | 14.25V |
| Charge compensation by temperature | ?5mV/°C per cell |
| Charge compensation for the 12V configuration | ?30mV/°C |
| Guide charging current | Between 10A and 50A for each 100Ah of nominal capacity |
| Operating temperature | From ?20°C to 45°C |
| Nominal operating temperature | From 10°C to 30°C |
| Recommended operating temperature | 20°C |
| Absolute maximum temperature | 55°C |
| Storage temperature | From ?40°C to 55°C |
| Maximum dimensions per cell | 147 × 208 × 690mm |
| Case height without terminals | 648mm |
| Installed length per cell | 156mm |
| Approximate weight per cell | 49kg |
| Approximate total weight of the 6 cells | 294kg |
| Terminals | F-M8 |
| Tightening torque of the M8 connections | 20 ± 1Nm |
| Case material | Styrene-acrylonitrile copolymer |
| Case flammability rating | UL 94 HB |
| Recommended minimum spacing between cells | 10mm |
| Recommended maximum temperature difference between cells | 3°C |
| Installation position | Vertical or horizontal |
| Approximate self-discharge | 2% per month at 20°C |