- Description
- Reviews (0)
Product description
Set comprising 48 MVSV gel cells of 2V and 1650Ah, supplied in 8 transport boxes. It allows battery banks of 12V, 24V, 48V or 96V to be configured by means of series and parallel connections. It is intended for large-capacity stationary systems that require reliable energy storage, continuous operation and flexibility to adapt the battery bank to the electrical characteristics of the installation.
Bank configurations
Connecting the 48 cells in series allows a bank of 96V and 1643Ah nominal to be configured. They can also be arranged in series-parallel configurations to increase the available capacity while maintaining a lower voltage:
- One series of 48 cells: 96V and 1643Ah nominal.
- Two series of 24 cells in parallel: 48V and 3286Ah nominal.
- Four series of 12 cells in parallel: 24V and 6572Ah nominal.
- Eight series of 6 cells in parallel: 12V and 13144Ah nominal.
In a series connection the voltages are added and the capacity is maintained. In parallel the voltage is maintained and the capacities are added. To ensure balanced operation, all series must incorporate the same number of cells and use units of the same range, model, capacity and state of charge. New cells must not be combined with used units.
Technology and installation
Valve-regulated lead-acid technology keeps the electrolyte immobilised in gel and does not require topping up with water. The cells can be installed in a vertical or horizontal position, always with the same orientation throughout the bank. In horizontal installations, each unit must be supported individually on a suitable rack along its entire surface.
Main features
- Set of 48 gel cells from the MVSV range.
- 96V configuration by connecting the 48 cells in series.
- Possibility of configuring banks of 48V, 24V or 12V by means of series-parallel connections.
- Valve-regulated lead-acid technology.
- Electrolyte immobilised in gel.
- No need to top up with water.
- Designed for large-capacity stationary systems.
- Installation permitted in a vertical or horizontal position.
- Approximate self-discharge of 2% per month at 20°C.
- Supplied in 8 transport boxes.
Technical specifications
| Parameter | Value |
|---|---|
| Range | MVSV |
| Technology | Valve-regulated lead-acid with gel electrolyte |
| Number of cells | 48 |
| Nominal voltage per cell | 2V |
| Commercial capacity per cell | 1650Ah |
| Technical nominal capacity per cell | 1643Ah in C10, up to 1.8V per cell at 20°C |
| Discharge current C10 per cell | 164A |
| 96V configuration | 1643Ah nominal |
| 48V configuration | 3286Ah nominal |
| 24V configuration | 6572Ah nominal |
| 12V configuration | 13144Ah nominal |
| Number of terminal pairs per cell | 2 |
| Internal resistance per cell | 0.23m? |
| Short-circuit current per cell | 9000A |
| Float voltage | 2.30V per cell at 25°C |
| Absorption voltage | 2.38V per cell at 25°C, for a maximum of 5 hours |
| Charge compensation by temperature | ?5mV/°C per cell |
| Guide charging current | Between 10A and 50A for each 100Ah of nominal capacity |
| Operating temperature | From ?20°C to 45°C |
| Nominal operating temperature | From 10°C to 30°C |
| Recommended operating temperature | 20°C |
| Absolute maximum temperature | 55°C |
| Storage temperature | From ?40°C to 55°C |
| Maximum dimensions per cell | 212 × 277 × 759mm |
| Case height without terminals | 717mm |
| Installed length per cell | 221mm |
| Approximate weight per cell | 115kg |
| Approximate total weight of the 48 cells | 5520kg |
| Terminals | F-M8 |
| Tightening torque of the M8 connections | 20 ± 1Nm |
| Case material | Styrene-acrylonitrile copolymer |
| Case flammability rating | UL 94 HB |
| Recommended minimum spacing between cells | 10mm |
| Recommended maximum temperature difference between cells | 3°C |
| Installation position | Vertical or horizontal |
| Approximate self-discharge | 2% per month at 20°C |