Set consisting of 6 MVSV gel cells of 2V and 280Ah, supplied in 1 transport box. Allows battery banks with different voltages and capacities to be configured by means of series and parallel connections.
Each cell has a nominal voltage of 2V and a capacity of 280Ah at C10. It is intended for stationary systems that require a high storage capacity, continuous operation and flexibility to adapt the battery bank to the electrical needs of the installation.
Bank configurations
The standard configuration connects the 6 cells in series to obtain a bank of 12V and 280Ah. Other combinations can also be made:
- Two strings of 3 cells connected in parallel: 6V and 560Ah.
- Three strings of 2 cells: 4V and 840Ah.
In a series connection the voltages are added and the capacity is maintained; in parallel the voltage is maintained and the capacities are added. The cells used in the same installation must be of the same model, capacity and state of charge.
Technology and installation
Valve-regulated lead-acid technology keeps the electrolyte immobilised in gel and does not require topping up with water. The cells can be installed in a vertical or horizontal position, always with the same orientation within the bank. When installed horizontally, they must rest individually on a suitable rack along their entire surface.
Main features
- Set of 6 gel cells from the MVSV range.
- Standard configuration of 12V and 280Ah.
- Possibility of creating other combinations by means of series and parallel connections.
- Valve-regulated lead-acid technology.
- Electrolyte immobilised in gel.
- No need to top up with water.
- Vertical or horizontal installation.
- Suitable for high-capacity stationary systems.
- Approximate self-discharge of 2% per month to 20°C.
- Supplied in 1 transport box.
Technical specifications
| Parameter | Value |
|---|---|
| Range | MVSV |
| Technology | Valve-regulated lead-acid with gel electrolyte |
| Number of cells | 6 |
| Nominal voltage per cell | 2V |
| Nominal capacity per cell | 280Ah at C10, up to 1.8V per cell at 20°C |
| Discharge current C10 per cell | 28A |
| Number of terminal pairs per cell | 1 |
| Internal resistance per cell | 0.79m? |
| Short-circuit current per cell | 2700A |
| Float voltage | 2.30V per cell at 25°C |
| Absorption voltage | 2.38V per cell at 25°C, for a maximum of 5 hours |
| Temperature charge compensation | ?5mV/°C per cell |
| Guide charge current | Between 10A and 50A for every 100Ah of nominal capacity |
| Operating temperature | From ?20°C to 45°C |
| Nominal operating temperature | From 10°C to 30°C |
| Recommended operating temperature | 20°C |
| Maximum absolute temperature | 55°C |
| Storage temperature | From ?40°C to 55°C |
| Maximum dimensions per cell | 126 × 208 × 399mm |
| Case height without terminals | 357mm |
| Installed length per cell | 135mm |
| Approximate weight per cell | 23kg |
| Approximate total weight of the 6 cells | 138kg |
| Terminals | F-M8 |
| Tightening torque of the M8 connections | 20 ± 1Nm |
| Case material | Styrene-acrylonitrile copolymer |
| Case flammability rating | UL 94 HB |
| Recommended minimum spacing between cells | 10mm |
| Recommended maximum temperature difference between cells | 3°C |
| Installation position | Vertical or horizontal |
| Approximate self-discharge | 2% per month to 20°C |