Set consisting of 48 MVSV 2V 2200Ah gel cells, supplied in 12 transport crates. It allows battery banks of 12V, 24V, 48V or 96V to be configured by means of series and parallel connections.
This set comprises 48 gel cells from the MVSV range, each with a nominal voltage of 2V and a commercial capacity of 2200Ah. It is intended for large-capacity stationary systems that require reliable energy storage, continuous operation and the flexibility to adapt the battery bank to the electrical characteristics of the installation.
Connecting the 48 cells in series allows a 96V, 2,190Ah nominal bank to be configured. They can also be arranged in series-parallel configurations to increase the available capacity while maintaining a lower voltage:
- One string of 48 cells: 96V and 2,190Ah nominal.
- Two strings of 24 cells in parallel: 48V and 4,380Ah nominal.
- Four strings of 12 cells in parallel: 24V and 8,760Ah nominal.
- Eight strings of 6 cells in parallel: 12V and 17,520Ah nominal.
In a series connection the voltages are added and the capacity is maintained. In parallel the voltage is maintained and the capacities are added. To ensure balanced operation, all strings must contain the same number of cells and use units of the same range, model, capacity and state of charge. New cells must not be combined with used units.
Valve-regulated lead-acid technology keeps the electrolyte immobilised in gel and does not require topping up with water. The cells can be installed in a vertical or horizontal position, always with the same orientation throughout the bank. In horizontal installations, each unit must be individually supported on a suitable rack over its entire surface.
The 48 cells are supplied in 12 transport crates.
Main features
- Set of 48 gel cells from the MVSV range.
- 96V configuration by connecting the 48 cells in series.
- Possibility of configuring 48V, 24V or 12V banks by means of series-parallel connections.
- Valve-regulated lead-acid technology.
- Electrolyte immobilised in gel.
- No need to top up with water.
- Designed for large-capacity stationary systems.
- Installation permitted in a vertical or horizontal position.
- Approximate self-discharge of 2% per month at 20°C.
- Supplied in 12 transport crates.
Technical specifications
- Range: MVSV.
- Technology: valve-regulated lead-acid with gel electrolyte.
- Number of cells: 48.
- Nominal voltage per cell: 2V.
- Commercial capacity per cell: 2200Ah.
- Nominal technical capacity per cell: 2,190Ah at C10, down to 1.8V per cell at 20°C.
- C10 discharge current per cell: 219A.
- 96V configuration: 2,190Ah nominal.
- 48V configuration: 4,380Ah nominal.
- 24V configuration: 8,760Ah nominal.
- 12V configuration: 17,520Ah nominal.
- Number of terminal pairs per cell: 3.
- Internal resistance per cell: 0.19m?.
- Short-circuit current per cell: 10750A.
- Float voltage: 2.30V per cell at 25°C.
- Absorption voltage: 2.38V per cell at 25°C, for a maximum of 5 hours.
- Temperature charge compensation: ?5mV/°C per cell.
- Recommended charge current: between 10A and 50A per 100Ah of nominal capacity.
- Operating temperature: from ?20°C to 45°C.
- Nominal operating temperature: from 10°C to 30°C.
- Recommended operating temperature: 20°C.
- Absolute maximum temperature: 55°C.
- Storage temperature: from ?40°C to 55°C.
- Maximum dimensions per cell: 216 × 400 × 816mm.
- Case height without terminals: 775mm.
- Installed length per cell: 225mm.
- Approximate weight per cell: 160kg.
- Approximate total weight of the 48 cells: 7,680kg.
- Terminals: F-M8.
- Tightening torque for M8 connections: 20 ± 1Nm.
- Case material: styrene-acrylonitrile copolymer.
- Case flammability rating: UL 94 HB.
- Recommended minimum spacing between cells: 10mm.
- Recommended maximum temperature difference between cells: 3°C.
- Installation position: vertical or horizontal.
- Approximate self-discharge: 2% per month at 20°C.
Be the first to leave your opinion