Set consisting of 12 MVSV 2V 420Ah gel cells, supplied in 1 transport box. Allows 12V or 24V battery banks to be configured by means of series and parallel connections.
This set brings together 12 gel cells from the MVSV range, each with a nominal voltage of 2V and a commercial capacity of 420Ah. It is intended for high-capacity stationary systems that require reliable energy storage, continuous operation and flexibility to adapt the battery bank to the characteristics of the installation.
The standard configuration connects the 12 cells in series to obtain a 24V, 416Ah nominal bank. They can also be arranged as two strings of 6 cells connected in parallel to configure a 12V, 832Ah nominal bank. In series the voltages add up and the capacity remains the same; in parallel the voltage remains the same and the capacities add up.
To ensure balanced operation, all connected cells and strings must be of the same range, model, capacity and state of charge. New cells must not be combined with used units.
Valve-regulated lead-acid technology keeps the electrolyte immobilised in gel and does not require topping up with water. The cells can be installed in a vertical or horizontal position, always with the same orientation within the bank. In horizontal installations, each unit must rest individually on a suitable rack along its entire surface.
The 12 cells are supplied in 1 transport box.
Main features
- Set of 12 gel cells from the MVSV range.
- Standard 24V configuration by means of series connection.
- Option to configure a 12V bank by means of two strings connected in parallel.
- Valve-regulated lead-acid technology.
- Electrolyte immobilised in gel.
- No need to top up with water.
- Designed for high-capacity stationary systems.
- Installation permitted in a vertical or horizontal position.
- Approximate self-discharge of 2% per month at 20°C.
- Supplied in 1 transport box.
Technical specifications
- Range: MVSV.
- Technology: valve-regulated lead-acid with gel electrolyte.
- Number of cells: 12.
- Nominal voltage per cell: 2V.
- Commercial capacity per cell: 420Ah.
- Technical nominal capacity per cell: 416Ah at C10, down to 1.8V per cell at 20°C.
- C10 discharge current per cell: 41.6A.
- Standard configuration: 24V and 416Ah nominal.
- Alternative configuration: 12V and 832Ah nominal.
- Number of terminal pairs per cell: 1.
- Internal resistance per cell: 0.62m?.
- Short-circuit current per cell: 3300A.
- Float voltage: 2.30V per cell at 25°C.
- Float voltage for the 24V configuration: 27.6V.
- Absorption voltage: 2.38V per cell at 25°C, for a maximum of 5 hours.
- Absorption voltage for the 24V configuration: 28.5V.
- Charge temperature compensation: ?5mV/°C per cell.
- Charge compensation for the 24V configuration: ?60mV/°C.
- Recommended charge current: between 10A and 50A per each 100Ah of nominal capacity.
- Operating temperature: from ?20°C to 45°C.
- Nominal operating temperature: from 10°C to 30°C.
- Recommended operating temperature: 20°C.
- Absolute maximum temperature: 55°C.
- Storage temperature: from ?40°C to 55°C.
- Maximum dimensions per cell: 126 × 208 × 515mm.
- Case height without terminals: 473mm.
- Installed length per cell: 135mm.
- Approximate weight per cell: 30kg.
- Approximate total weight of the 12 cells: 360kg.
- Terminals: F-M8.
- Tightening torque for M8 connections: 20 ± 1Nm.
- Case material: styrene-acrylonitrile copolymer.
- Case flammability rating: UL 94 HB.
- Recommended minimum spacing between cells: 10mm.
- Recommended maximum temperature difference between cells: 3°C.
- Installation position: vertical or horizontal.
- Approximate self-discharge: 2% per month at 20°C